• IEC60584-1 Programmable Automatic Door and Curtain Fire Resistance Test/Testing Machine
  • IEC60584-1 Programmable Automatic Door and Curtain Fire Resistance Test/Testing Machine
  • IEC60584-1 Programmable Automatic Door and Curtain Fire Resistance Test/Testing Machine
  • IEC60584-1 Programmable Automatic Door and Curtain Fire Resistance Test/Testing Machine

IEC60584-1 Programmable Automatic Door and Curtain Fire Resistance Test/Testing Machine

Warranty: 12 Months
Equipment Measuring Precision: ±15ºC
Sample Inner Temperature: ±10ºC
Sample Back Fire Temperature: ±4ºC
Timing Range: 0~300 Min
Timing Precision: <±1s
Customization:
Manufacturer/Factory & Trading Company
Gold Member Since 2018

Suppliers with verified business licenses

Guangdong, China
Importers and Exporters
The supplier has import and export rights
High Repeat Buyers Choice
More than 50% of buyers repeatedly choose the supplier
Cooperated with Fortune 500
This supplier has Cooperated with Fortune 500 companies
Years of Export Experience
The export experience of the supplier is more than 10 years
to see all verified strength labels (30)

Basic Info.

Model NO.
SH5729A/B
Function
Door and Curtain Fire Resistance Testing
Delivery
Within 10-40 Working Days After Order Confirmed
Shipment
Ocean or The Customer′s Requirement
Transport Package
Wooden Box
Specification
2100*2100*2100mm
Trademark
Sunho
Origin
China Mainland
HS Code
9031809090
Production Capacity
1500 Set Per Year

Product Description

IEC60584-1 Programmable Automatic Door and Curtain Fire Resistance Test/Testing Machine

1. Product Description

The device is designed according to the relevant requirement of the standard IEC60584-1 and EN1634-1 and so on.

2. Standards

IEC60584-1, EN1634-1

3. Technical Parameters

The device equipped with:

1)combustion furnace
 
Power supply AC380V±10%   50Hz
Test temperature control the furnace temperature meets the requirement of T-T0=345lg(8t+1)
Equipment measuring precision ±15ºC
Sample inner temperature ±10ºC
Sample back fire temperature ±4ºC
Timing range 0~300 min
Timing precision <±1s
Furnace inner pressure meeting Five minutes after the experiment started, the furnace should meet the normal positive pressure condition as follow.
Component in the furnace 3m height, 100mm from the surface of the sample, the furnace pressure is 15Pa±5Pa
Ten minutes after the experiment started, the furnace should meet the normal positive pressure condition as follow Component---in the furnace 3m height, 100mm from the surface of the sample, the furnace pressure is 17Pa±3Pa.
Sample receiving layer surface fire doors maintain a positive pressure over the entire height, the other ridge pressure maintained within the range 20±2Pa, the furnace pressure gradient per meter 8Pa.
Temperature measuring sensor: the performance, number and location of the thermocouple in the heating furnace meet the requirements in the standard.

2)Gas system
 
Flue gas and vaporizer equipped with automatic switching valve to the gas automatic switch. Equipped with gas-saving device, equipped with flammable gas leak alarm device.
Air source system Using high-pressure centrifugal fan + inverter to regulate flow and pressure.

3)Environmental protection and fire alarm device
 
Flue gas spray, environmental protection system ≥5000m³/h, smoke treatment per hour: 4000~12000m³.

4)control analysis system
 
Test control system consists of pressure sampling system, temperature sampling control system, signal acquisition system, computer system, testing and sampling circuit.
The electrical signals generated by the thermocouple can be sent directly to the recorder or computer via the temperature transmitter. During the test, the average temperature, the single-point temperature and the amount of leakage are displayed.
Test start and process control, test parameter settings, various types of test data is sent to the computer through the sensor sampling, and it can be stored and printed into a table(graph) after the computer automatically calculated and processed. Software can be programmed automatically according to the temperature curve, and record their own furnace temperature, furnace pressure, sample back temperature and other data.
Computer monitoring system provides query function. System automatically number the sample, temperature curve and data is stored in the system's database, and it can be queried by entering the test sample number, test data and other inquiries. It is equipped with standard RS-232 interface and USB interface.
The pressure difference between the measuring device and ambinet atmospheric pressure is monitored. The device with security alarm function, over temperature protection alarm function.
SH5729B elevator door test needs to detect smoke and gas leakage. The system uses carbon dioxide as the tracking gas, measuring the gas concentration in the heating furnace and the air flow measurement point, and calculates the leakage amount of the hot air the landing door by monitoring the air flow velocity and temperature.

IEC60584-1 Programmable Automatic Door and Curtain Fire Resistance Test/Testing MachineIEC60584-1 Programmable Automatic Door and Curtain Fire Resistance Test/Testing MachineIEC60584-1 Programmable Automatic Door and Curtain Fire Resistance Test/Testing MachineIEC60584-1 Programmable Automatic Door and Curtain Fire Resistance Test/Testing MachineIEC60584-1 Programmable Automatic Door and Curtain Fire Resistance Test/Testing MachineIEC60584-1 Programmable Automatic Door and Curtain Fire Resistance Test/Testing MachineIEC60584-1 Programmable Automatic Door and Curtain Fire Resistance Test/Testing Machine

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now